187 kVA Diesel Generator - Agrison Temporary Power Generator

$18,172.73 AUD

($19,990 AUD GST Inclusive)

Seller confirm cost

Get a Finance Quote

187 kVA Diesel Generator - Agrison Temporary Power Generator Specification Download PDF brochure.

  • Make : AGRISON
  • Model : 187 kVA Diesel Generator
  • Subcategory : Temporary Power Generator
  • Condition : New
  • Electrical-Phase : Three Phase

Description

Specifications

ELECTRICAL
FREQUENCY: 50HZ 3 PH
VOLTAGE: 415V/230V
PRIME: 187KVA/150KW
STANDBY: 205KVA/165KW
Rated Speed: 1500RMP-50HZ
Circuit Breaker: 4 Poles
Power Factor: 0.8--3 Phase

ALTERNATOR
Model: YHG-150KW
Poles: 4 poles
Winding Connections: star
Insulation: Class H
Enclosure: IP23
Exciter System: Self-regulating brushless
Voltage Regulator: AVR
Steady State Voltage Regulation: +/- 1.0%
Bearing Single: bearing sealed
Coupling: Flexible disc
Cooling direct: drive centrifugal blower fan

ENGINE
R6105AZLD: 50 HZ
Output Rating: 155 kw
Manufacturer and model: Weifang
Fuel: Diesel
Injection: in-line
Aspiration: turbo charger inter cool
Cylinders: 6
Bore and Stroke: 113*125 mm
Displacement: 6.75 L
Cooling: Water cooling
Engine Oil Specification: SAE 3/11.5
Compression Ratio: 16:1
Engine Oil Capacity: 17 L
Governor: Mechanical
Air Filter: Dry
Fuel Consumption
100% Load Prime: 215 G/KW.H
75% Load Prime 161.2 G/KW.H
50% Load Prime: 107.5 G/KW.H
100% Load Standby: 236.5 G/KW.H

EXHAUST SYSTEM
Maximum Temperature 100% Standby: 420
Exhaust Flange Size(Internal Diameter): 760 mm

STARTING SYSTEM
Starter Motor: KW
Battery Capacity: 100 AH
Auxiliary Voltage: 12V

FUEL SYSTEM
Fuel Tank Capacity: 8 HOURS

WEIGHT AND DIMENSIONS - OPEN
Length: 2900 mm
Width: 1200 mm
Height: 1500 mm
Wet Weight(Standard Build): 1700 kg
Dry Weight(Standard Build): 1650 kg

WEIGHT AND DIMENSIONS - CANOPY
Length: 3200 mm
Width: 1250 mm
Height: 1700 mm
Wet Weight(Standard Build): 1850 kg
Dry Weight(Standard Build): 1800 kg
Sound pressure(LpA) - 7m: 70 DB

Alarms and shutdown functions (S-Shutdown A - Alarm)
High Coolant Temperature: S
Low Oil Pressure: S
Unexpected Shutdown: A
Battery Charge Alternator Failure: A
Over Speed: S
Failure to Start: A
Emergency Stop: A
Alternator-high Frequency: S

Contact

1300651830  